Low resistancer, the the initial resistance is about 15Pa.Product features
Product material |
Performance and graph |
Media material : |
Ultra low resistance filter media |
Frame material : |
Galvanized steel / Aluminum |
Sealant : |
Pu two-component polyurethane glue |
Max operating temperature : |
70°C |
Low resistancer, the the initial resistance is about 15Pa.Product features
1.Adopt the ultra-low resistance filter material, high filtration efficiency, stable and reliable performance.
2. Ultra-low resistance filtration, low system energy consumption, and easy installation.
3.Compared with ordinary filters, the replacement cycle is longer and the maintenance cost is lower.
Efficiency:
≥0.3um | ≥0.5um | ≥0.7um | ≥1.0um | ≥2.0um | ≥5.0um |
74.8 | 85 | 87.4 | 89.8 | 93.8 | 95.8 |
Model |
Overalldimensions (mm)(WxHxD) |
Filter Size (mm)(WxHxD) | Rated air flow/Wininitial resistance(m/h)/(pa) | Wind speed(m/s) | Filter area(m² ) | Filtrationefficiency(0.5um) |
BAC-1600 | 1150x550x300 | 1100x500x100 | 1600/20 | 0.8 | 7.6 | >80% |
BAC-1500 | 1050x550x300 | 1000x500x100 | 1500/20 | 0.8 | 6.8 | >80% |
BAC-1200 | 950x550x300 | 900x500x100 | 1200/20 | 0.8 | 6.1 | >80% |
BAC-1000 | 750x550x300 | 700x500x100 | 1000/20 | 0.8 | 4.8 | >80% |
BAC-800 | 550x550x300 | 500x500x100 | 800/20 | 0.8 | 3.4 | >80% |